Specifications

Absolute Maximum Ratings Min Typ Max
Applied power supply (VPS) 18 VDC 24 VDC 27 VDC
Applied output voltage - Note 2 0 VDC   VPS VDC
Output current      
Single output     500 mA DC
Total limit   5 A DC  
Specifications      
Current requirement (VPS = 24 V) 50 mA 100 mA 210 mA
User memory capacity     24K bytes
(10 year battery backed RAM)      
Input "off" voltage (Ii = 0 mA)   VPS VDC  
Input "on" current (Vi = 0 V with VPS = 24 V   -2.3 mA CD -3.00 mA DC
Input "on" current threshold (VPS = 24 V)   -1.3 mA DC -1.75 mA DC
Input "off" current (typical leakage allowed)     250 μA
Output "on" voltage (Io = 500 mA) 0.6 VDC 0.8 VDC 1.2 VDC
Output "off" leakage (applied V = 24 V) 0.01 μA DC   0.75 μA DC

Note 1. Under normal operation, no external input voltage should be applied — inputs should be externally switched to the input common.
Note 2. An onboard protection diode returns to +24 V from each output.
Note 3. All power requirements are worst case with all inputs and outputs activated.